Skip to content

Remote Zone Sensor with Setpoint Adjustment

TS2023a

Description

1000 ohm platinum RTD zone temperature sensor with override and setpoint for use with the SZ1025b. Sensor is enclosed in a ventilated ASB plastic housing with a plastic base. Units are suitable for mounting to dry wall or block, or to a standard 2″ X 4″ handy box using a TQ Series plate adapter. 

Single-point sensor accuracy:

+/–0.1% @ 32°F (0°C)

Temperature coefficient: 

0.00385 Ω/Ω/°C

Reference resistance: 

1000Ω @ 32°F (0°C)

Compliance:

DIN IEC 751

Response time (90%):

  • Air @1m/s: 25 seconds
  • Air @3m/s: 17 seconds

Operating temperature:

–50 to 375°F (–45.6 to 190.6°C)

Maximum current:

5 mA; recommended: 1 mA

Contact Us