Skip to content

Differential Pressure Transducer

TL1160

Description

The TL1160 Pressure Transducer provides accurate pressure measurement for duct static pressure, building pressurization, and other differential air flow systems. Its differential pressure range is –0.25 to +0.25", +0.75" or +1.75" WCD.

The TL1160 is functionally identical to the TD1190 Pressure Transducer, which has a differential pressure range of 0 – 1", 2" or 3" WCD.

Specifications

Accuracy:

+/– 1% of span @77°F (25°C)

Linearity:

+/– 0.2% FSO

Repeatability:

+/– 0.05% FSO

Hysteresis:

+/– 0.025% FSO

Thermal Effects:

+/– 0.06% FSO/°F (+/– 0.10% FSO/°C) relative to 69°F (20°C)

Media compatibility: 

Non-ionic, non-corrosive gases

Supply Voltage:

12 – 35 VDC

Output:

4 – 20 mA DC, 2-wire

Polarity Protection:

Diode protected

Contact Us