Differential Pressure Transducer
TD1190Description
The TLD1190 Pressure Transducer provides accurate pressure measurement for duct static pressure, building pressurization, and other differential air flow systems. Its differential pressure range is 0 – 1", 2" or 3" WCD.
The TD1190 is functionally identical to the TL1160 Pressure Transducer, which has a differential pressure range of –0.25 to +0.25", +0.75" or +1.75" WCD.
Linearity:
+/– 0.2% FSO
Repeatability:
+/– 0.05% FSO
Hysteresis:
+/– 0.025% FSO
Thermal Effects:
+/– 0.06% FSO/°F (+/– 0.10% FSO/°C) relative to 69°F (20°C)
Media Compatibility:
Non-ionic, non-corrosive gases
Supply Voltage:
12 – 35 VDC
Output:
4 – 20 mA DC, 2-wire
Polarity Protection:
Diode protected
Specs & Docs
Specifications:
General
Accuracy: +/-1% of span @ 77°F (25°C)
Linearity: +/-0.2% FSO
Repeatability: +/-0.05% FSO
Hysteresis: +/-0.025% FSO
Thermal Effects: +/- 0.06% FSO/°F (+/- 0.10% FSO/°C) relative to 69°F (20°C)
Media compatibility: Non-ionic, non-corrosive gases
Environmental
Operating temperature: 32 to 122°F (0 to 50°C)
Operating humidity: 0 to 100% RH, non-condensing
Storage temperature: 14 to 176°F (-10 to 80°C)
Electrical
Supply voltage: 12 to 35 VDC
Input voltage effect: +/-0.001% of span/volt
Output: 4 to 20 mA DC, 2-wire
Polarity protection: Diode protected
Specifications subject to change without notice.